  • DP_Joci

    tag

    válasz Szirty #3837 üzenetére

    Szia Szirty,

    Amikor arra gondoltam, hogy megkeresed a nullás címet, akkor az AS-i masteren gondoltam, hogy a nullás AS-i címet keresed meg.

    Találtam egy manualt: C79000−G8976−C149−04 google-ba beírva az első pdf nálam.
    De az a lényeg, hogy gomb nyommással elméletileg lehet a meglévő slave címeket megjeleníteni, és emlékeim szerint változtatni is:

    Configuring using Buttons
    Preparation for Button Configuration
    Make sure that the following situation applies:
    _ The PLC CPU must be switched to STOP.
    _ The CP 343-2 and all AS-i slaves must be connected to the AS-interface and
    supplied with power.
    _ The AS-i slaves must have unique addresses other than “0”.
    Setting the Configuration with Buttons
    1. Check whether the CP 343-2 is in “configuration mode” (”CM” LED is lit).
    If the ”CM” LED is not lit, change the CP 343-2 to the configuration mode with
    the “SET” button.
    2. Check whether all the slaves connected to the AS-interface exist and are
    displayed.
    3. Press the SET button. This configures the CP 343-2; in other words, the
    detected actual configuration is stored as the default in the non-volatile
    EEPROM. At the same time, the CP 343-2 is changed to the protected mode;
    the “CM” LED goes off. (See Section 1.5 > SET button)
    The “CER” LED also goes off since following configuration, the “expected
    configuration” stored on the CP 343-2 matches the “actual configuration” on the
    AS-Interface.
    Note
    Changing from the configuration mode to the protected mode is only possible
    when there is no AS-i slave with address 0 connected to the AS-Interface. If a
    slave 0 is connected, the “SF” LED lights up when the SET button is pressed.
    If you run a button configuration when there is no AS-i power supply (APF state) or
    when no AS-i slaves are connected, all the internal lists are set to their default
    values. In particular, all the AS-i parameters are set to = FHex and the
    AutoAddress_Enable bit is set to = 1.

    Egyébként ezzel egyszerűbb:

    http://www.ifm.com/products/hu/ds/AC1154.htm